Features:
- Large versatile touch-screen user interface
- 2 or 4 Class A Style 7 SLC loops
- Event history buffer (9,999 events) with date/time stamp
- 4 Notification appliance circuit (NAC’s) outputs
- Dedicated alarm, trouble, AC trouble relays
- Integral short circuit isolators
- Up to 200 addresses per loop
- Full network capability up to 126 panels
- Supports a comprehensive range of soft addressing modules and devices for greater flexibility in design
- Menu driven graphical user interface for ease of operation
- Reduced commissioning time through soft addressing and auto learn functions
- Programming and trouble shooting time minimised by using a range of features such as auto config, walk test, system details menus
Specifications:
Code ULCF3000 / ULCF3000RM
Description UL intelligent addressable control panel
Standards UL864 9th edition
Primary operating supply 120V ac / 240V ac, 60Hz, 2.0A supervised
Secondary operating supply
Battery voltage 24V dc
Battery charge current 1.0A (max)
Battery derating factor 0.1
Battery capacity supervised 12Ah (max)
Notification appliance circuits Class B, Style Y, Sounder Group 1, Sounder 1, Sounder Group 1, Sounder 2, Sounder Group 2
Output voltage 24V dc
Output current 0.75A (max)
Line impedance 50Ω
When powered by 240V ac, the maximum
current of 3.0A is shared between these
circuits
When powered by 120V ac, the maximum
current of 2.25A is shared between these
circuits
Circuits are supervised, power limited and
regulated.
Notification appliance circuits Class B, Style Y, SYNC MODULE. NAC1,
NAC2
Output voltage 24V dc
Output current 0.5A (max)
Line impedance 50Ω (max)
The maximum current of 0.5A is shared
between these circuits
Circuits are supervised, power limited and
regulated.
Alarm, trouble contacts. Relay expansion
Unity power factor 30V dc
For connection to power limited sources only
Aux relay (AC Trouble) contacts
Unity power factor 30V dc, 1A
For connection to power limited sources only
Signaling line circuit Style [7] Class [A] – (Addressable Loop)
Rated voltage 24V dc
Maximum current 500mA
Line impedance 50Ω (max)
Supervised, power limited
Network SLC
Voltage 5V dc
Current 100mA (max)
Line impedance 50Ω (max)
Power limited
Limited to same enclosure installations
Physical
IP Rating IP30
Compatibility
Suitable for use with Eaton UL fire systems